Room conditions
Room temperature too high
Pressure drop across evaporator too high.
Lack of subcooling ahead of expansion valve.
Pressure drop across expansion valve less than pressure drop valve is sized for.
Bulb located too cold, e.g. in cold air flow or near large valves, flanges, etc.
Expansion valve blocked with ice, wax or other impurities.
Expansion valve too small.
Charge lost from expansion valve.
Charge migration in expansion valve.
Expansion valve bulb not in good contact with suction line.
Evaporator completely or partly iced up.
KVP evaporating pressure regulator set too high.
Bellows leak in KVP evaporating pressure regulator.